*How to connect 4203DR AOUT to SP350 AIN using I-I Isolator?*
AOUT on 4203 cannot be connected directly to AIN on the SP350 because both are current sinking type of I/O.

Drawing shown below describes how AOUT on 4203DR transmitter should be connected to AIN on SCADAPack 350 when I-I Isolator is used. Jumper must be in the Current position.
\\ !worddav88f236da6948d604e9c16a810d13a940.png|height=173,width=539!
\\ !worddav0770a9f937e7aaaef9a37e3b58abe823.png|height=243,width=575!
\\
*Drawing shown below describes how AOUT on 4203DR transmitter should be connected to AIN on SCADAPack 350 when I-I Isolator is used. Jumper must be in the Current position.*
\\
!worddav88f236da6948d604e9c16a810d13a940.png|height=173,width=539!
\\
!worddav0770a9f937e7aaaef9a37e3b58abe823.png|height=243,width=575!
\\