Problem

I have a SCADAPack32/SCADAPack350. After a cold boot, can I communicate to it directly on the LAN port?

Environment

SCADAPack32
SCADAPack350
TelePACE
ISaGRAF

Fix

When a SCADAPack32/SCADAPack350 is at its factory default settings, the IP address of the LAN port is set to 0.0.0.0. In order to communicate to the SCADAPack32 via the LAN port, you must first connect to it using a serial cable and download a valid IP address. Once the IP address has been written to the controller, you may then communicate to it via ethernet to the LAN port.